The manual balancing valve STV(E) is optimized for use in heating- and cooling systems.

Description
STV(E) are sized with nomogram, handwheel or online Applications on smartphones or on our webside.
STV(E) shall be dimensioned at 50-80% of maximum flow for the design flow.
Minumum recommended differential pressure is 2 kPa (0,29 psi)

Properties
Max operating temperature 110
Pressure rating PN16