The diverters are available in two versions, FA – for 2-pipe system and FEA – for 1-pipe system. The diverters are reversible for ground/top or side connection and have a built-in shutdown. The connection to the pipe system is M22x1,5. The diverter is equipped with a spindle for shutdown, hidden behind a lid. (key grip Allen key 10 mm) For the FA diverter, 2-pipe, both the supply and return are closed when the spindle is in the screwed-in position. For the FEA diverter. 1-pipe ground connected, the return line i closed in screwed-in mode while closing the supply with the thermostatic head, hand wheel or protective cap. The circulation in the loop of the 1-pipe diverter FEA is always open, regardless of whether the diverter is closed or open. When assembling, always follow the flow direction lines on the diverter so that the supply enters the top of the raditor. NOTE: Side-connected FEA can not be turned off.